Description
Mechanical Design :
Units of plug-in design like their predecessor types LGB and LMG (see Dimensions)
Burner controls LME and plug-in base AGK11 are black
The housing is made of impact-proof, heat-resistant and flame-retarding plastic. It is of plug-in design and engages audibly in the base
The housing accommodates the – microcontroller for the control sequence and the control relays for load control – electronic flame signal amplifier (ionization) – Lockout reset button with integrated 3-color signal lamp (LED) for operating status and fault status messages and the socket for connecting the OCI400 optical interface or the AGK20 lockout reset button extension
All safety-related digital inputs and outputs of the system are monitored by means of a contact feedback network
Burner capacity unlimited (thermal output on startup
120 kW)
3 restarts in the event of loss of flame during operation (LME11/LME41.051)
Restart in the event of loss of flame during operation (LME41.052/LME41.053/LME41.054/LME41.071/LME41.091/ LME41.092/LME44.190)
Multicolor display of operating status and fault status messages via integrated 3- color signal lamp (LED) in the lockout reset button Operating status messages, fault status messages, and service information are transmitted via a unidirectional interface (UDS) in diagnostic mode. An OCI400 optical interface is used for this, which is attached to the lockout reset button and features an integrated LED signal lamp. The OCI400 then transmits the information to the ACS410 PC software or to flue gas analyzers from various manufacturers
The ACS410 PC software offers straightforward operation via the OCI400 optical interface, convenient readout of settings and operating states, trend recordings, and targeted diagnostics of the LME